140G-K6F3-D30 Allen-Bradley 400A K-Frame Molded Case Circuit Breaker, 300A Thermal Magnetic, 65kA at 480V – Surplus
Get a quote on 140G-K6F3-D30
- A real person replies with price and availability
- Trusted by customers since 1987
- Need a different series, revision or quantity? Just ask
The 140G-K6F3-D30 is an Allen-Bradley 400A K-Frame Molded Case Circuit Breaker, 300A Thermal Magnetic, 65kA at 480V. It is part of our Allen-Bradley surplus inventory in Jamestown, New York.
Rockwell Automation catalog description: 140G - Molded Case Circuit Breaker, K frame, 65 kA Interrupt Rating, T/M - Thermal Magnetic, 3 Poles, Rated Current 300 A (80% Rated).
Request a quote or call 1-800-724-4209 for price, condition and quantity. A real person at United Industries will reply.
140G-K6F3-D30 specifications
| Catalog number | 140G-K6F3-D30 |
|---|---|
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product family | Molded Case Circuit Breakers |
| Product name | 140G 400A K Frame Molded Case Ckt-Bkr |
| Description | 140G - Molded Case Circuit Breaker, K frame, 65 kA Interrupt Rating, T/M - Thermal Magnetic, 3 Poles, Rated Current 300 A (80% Rated) |
| Rockwell lifecycle status | Active |
| Ambient temperature without derating | 104 °F |
| Complete device with protection unit | Yes |
| Current range | 80% MCCB |
| Degree of protection (IP) | IP40 |
| Depth | 108.5 mm |
| Device construction | Built-in device fixed built-in technique |
| DIN rail (top hat rail) mounting optional | No |
| Electrical life cycle | 7000 (400 A)/5000 (600 A) @ 415V AC |
| Factory option | None |
| Frame size | 400 A |
| Height | 205 mm |
| Insulation voltage (Ui) | Rated 1000V per IEC |
| Integrated earth fault protection | No |
| Interrupting rating | 65kA @ 480V AC, 50/60 Hz per NEMA, UL, CSA |
| Magnetic trip current (Im) | 1500 A |
| Mechanical life operations | 20000 /h |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Number of poles | 3 |
| Operational voltage (Ue) | 90% of voltage rating @ 3000 m (9840 ft) altitude |
| Position of connection for main current circuit | Front side |
| Protection type | T/M-adjustable thermal/adjustable magnetic TMA |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated permanent current Iu | 300 A |
| Rated service short-circuit breaking capacity (Ics) | IEC 60947-2: 100% Icu @ 750V DC, 3-poles in series, thermal-magnetic trip units only |
| Rated ultimate short-circuit breaking capacity (Icu) | IEC 60947-2: 70kA @ 400...415V AC, 50/60 Hz |
| Rated uninterrupted current (Iu) | 98% of current rating @ 3000 m (9840 ft) altitude |
| Shock | Peak acceleration: 150 m/s² peak, pulse duration 11 ms |
| Storage temperature | -40 °F |
| Suitable for DIN rail (top hat rail) mounting | No |
Specifications are from Rockwell Automation's published product data. Check them against your application before you order.
Questions about the 140G-K6F3-D30
How do I get a price on the 140G-K6F3-D30?
Request a quote with the quantity you need, or call 1-800-724-4209. A real person at United Industries will reply with price and availability.
Is the 140G-K6F3-D30 new?
This is a surplus part. Its condition is listed in the title and description. If you need photos, date codes or more detail, ask us.
Does it come with a warranty?
Yes. Every Surplus Allen-Bradley part we sell includes a 1-year United Industries warranty.
Do you need a different series, revision or quantity?
Tell us exactly what you need in your quote request or by phone. If it isn't listed, we'll try to track it down for you.
Where do you ship from?
We ship from Jamestown, New York, to customers across the United States and to many countries worldwide.
Who is United Industries?
An industrial automation and electrical parts supplier in Jamestown, NY, serving customers since 1987. More about us.
Have spare parts you no longer need?
We buy surplus. Send us your list and we'll make you an offer.
Also searched as: 140GK6F3D30, 140G K6F3 D30, I40G-K6F3-D30, I40GK6F3D30, 14OG-K6F3-D3O